Home » Blogs » Electrical Knowledge » What Size Automatic Transfer Switch Do You Need for Your Generator?

What Size Automatic Transfer Switch Do You Need for Your Generator?

Views: 0    

facebook sharing button
twitter sharing button
linkedin sharing button
sharethis sharing button

Need a transfer switch for your generator but unsure what amp rating to choose? This guide will help you find a suitable automatic transfer switch .

For a quick answer, jump straight to the sizing chart below. If you’d like to understand how the figures are calculated, follow the guide step by step.

1. Check the Generator Nameplate

Start with the information on your generator’s nameplate.

You need four details:

(1)electrical output in kVA or kW,

(2)rated voltage,

(3)single-phase or three-phase configuration, and

(4)rated power factor if using kW.

600kw silent diesel generator 01

2. Calculate Generator Current: kVA or kW to Amps

Three-phase generators

From kVA: Current (A) = kVA × 1,000 ÷ (√3 × voltage)

From kW: Current (A) = kW × 1,000 ÷ (√3 × voltage × power factor)

Here, √3 ≈ 1.732, and voltage means line-to-line voltage. Use 380V for a 380/220V system or 400V for a 400/230V system.

Single-phase generators

From kVA: Current (A) = kVA × 1,000 ÷ voltage

From kW: Current (A) = kW × 1,000 ÷ (voltage × power factor)

For example, a 10 kW single-phase generator at PF 1.0 delivers approximately 45.5A at 220V or 43.5A at 230V.

Which power factor should you use?

Use the value on the generator nameplate. If it states PF 0.8, then:

100 kVA × 0.8 = 80 kW

Do not divide by power factor again when calculating from kVA. No efficiency factor is needed when using rated electrical output. Power factor and any planning allowance are separate inputs, not interchangeable “safety factors.”

3. Find an Initial ATS Size in the 380V / 400V Chart

The table assumes balanced three-phase output; the kW equivalents use PF 0.8.

Generator (kVA)

kW at PF 0.8

Current at 380V (A)

Current at 400V (A)

Initial ATS Size (A)

20

16

30.4

28.9

32

30

24

45.6

43.3

50

40

32

60.8

57.7

63

50

40

76.0

72.2

80

62.5

50

95.0

90.2

100

80

64

121.5

115.5

125

100

80

151.9

144.3

160

125

100

189.9

180.4

200

160

128

243.1

230.9

250

200

160

303.9

288.7

315

250

200

379.8

360.8

400

320

256

486.2

461.9

500

400

320

607.7

577.4

630

500

400

759.7

721.7

800

630

504

957.2

909.3

1,000

800

640

1,215.5

1,154.7

1,250

1,000

800

1,519.3

1,443.4

1,600

Real example: What size ATS does a 600 kW generator need?

600KW diesel generator.jpg

This is one unit of 600KW silent disel generator set in our customer's factory.

For 600 kW, 400V, three-phase, PF 0.8:

Current = 600 × 1,000 ÷ (√3 × 400 × 0.8) ≈ 1105.8A

At 380V, the current is approximately 1139.4A.

For both 380V and 400V systems, you can start by considering a 1200 amp automatic transfer switch.

AISIKAI supplied the 1250A automatic transfer switch (ATS) shown below to customer.

1250Amp automatic transfer switch for generator

Also note that 600 kW and 600 kVA are different ratings: at PF 0.8, 600 kW equals 750kVA. Use the correct row or formula.

Can the Same ATS Work with 220V/380V and 230V/400V?

AISIKAI SKT1 supports both 220V and 230V AC control supplies.

4. Confirm the ATS Rating for the Installation

Check these five points before turning the calculated candidate into a final selection:

  • Check the load on mains power, too.

    Some systems turn off less important equipment when the generator takes over. This allows a smaller generator to be used. But the transfer switch still needs to carry the full load when mains power is on

  • Temperature: High temperatures may reduce how much current the ATS can carry. Check the manufacturer’s guidance.

  • Future expansion: If you plan to add more equipment later, choose an ATS with extra capacity.

  • Protection: PC-class automatic transfer switches do not have built-in overload or short-circuit protection. Use suitable circuit breakers or fuses to provide this protection.

  • Poles and controls: confirm neutral switching, frequency, control voltage and the generator-start interface. The current calculation does not determine whether the system needs three or four poles.

Choose an AISIKAI Transfer Switch for Your Generator

Once you know the required amp rating, you can compare these options:

Need More Than 3200A?

AISIKAI offers two options, both available up to 6300A:

Need a Complete ATS Cabinet?

We also offer complete automatic transfer switch cabinets. Tell us your required amp rating and site needs. We can build the cabinet with a suitable switch, controller and protection devices.

Frequently Asked Questions

Can I use an ATS with a higher amp rating than my generator?

Yes. A higher-rated ATS is fine, but it does not let your generator power more equipment. Keep the total load within the generator’s rated capacity.

Does 50Hz or 60Hz affect ATS selection?

The current calculation is the same for both. AISIKAI SKT1 works with 50Hz and 60Hz. If you also need a controller, tell us the frequency when ordering so we can set it before delivery.

Get Help Selecting Your ATS

Send your generator nameplate or configurations to sales@aisikai.com.

Include a single-line diagram if available. Tell us whether you need a standalone switch or a complete ATS cabinet.