Need a transfer switch for your generator but unsure what amp rating to choose? This guide will help you find a suitable automatic transfer switch .
For a quick answer, jump straight to the sizing chart below. If you’d like to understand how the figures are calculated, follow the guide step by step.
Start with the information on your generator’s nameplate.
You need four details:
(1)electrical output in kVA or kW,
(2)rated voltage,
(3)single-phase or three-phase configuration, and
(4)rated power factor if using kW.
From kVA: Current (A) = kVA × 1,000 ÷ (√3 × voltage)
From kW: Current (A) = kW × 1,000 ÷ (√3 × voltage × power factor)
Here, √3 ≈ 1.732, and voltage means line-to-line voltage. Use 380V for a 380/220V system or 400V for a 400/230V system.
From kVA: Current (A) = kVA × 1,000 ÷ voltage
From kW: Current (A) = kW × 1,000 ÷ (voltage × power factor)
For example, a 10 kW single-phase generator at PF 1.0 delivers approximately 45.5A at 220V or 43.5A at 230V.
Use the value on the generator nameplate. If it states PF 0.8, then:
100 kVA × 0.8 = 80 kW
Do not divide by power factor again when calculating from kVA. No efficiency factor is needed when using rated electrical output. Power factor and any planning allowance are separate inputs, not interchangeable “safety factors.”
The table assumes balanced three-phase output; the kW equivalents use PF 0.8.
Generator (kVA) | kW at PF 0.8 | Current at 380V (A) | Current at 400V (A) | Initial ATS Size (A) |
|---|---|---|---|---|
20 | 16 | 30.4 | 28.9 | 32 |
30 | 24 | 45.6 | 43.3 | 50 |
40 | 32 | 60.8 | 57.7 | 63 |
50 | 40 | 76.0 | 72.2 | 80 |
62.5 | 50 | 95.0 | 90.2 | 100 |
80 | 64 | 121.5 | 115.5 | 125 |
100 | 80 | 151.9 | 144.3 | 160 |
125 | 100 | 189.9 | 180.4 | 200 |
160 | 128 | 243.1 | 230.9 | 250 |
200 | 160 | 303.9 | 288.7 | 315 |
250 | 200 | 379.8 | 360.8 | 400 |
320 | 256 | 486.2 | 461.9 | 500 |
400 | 320 | 607.7 | 577.4 | 630 |
500 | 400 | 759.7 | 721.7 | 800 |
630 | 504 | 957.2 | 909.3 | 1,000 |
800 | 640 | 1,215.5 | 1,154.7 | 1,250 |
1,000 | 800 | 1,519.3 | 1,443.4 | 1,600 |
This is one unit of 600KW silent disel generator set in our customer's factory.
For 600 kW, 400V, three-phase, PF 0.8:
Current = 600 × 1,000 ÷ (√3 × 400 × 0.8) ≈ 1105.8A
At 380V, the current is approximately 1139.4A.
For both 380V and 400V systems, you can start by considering a 1200 amp automatic transfer switch.
AISIKAI supplied the 1250A automatic transfer switch (ATS) shown below to customer.
Also note that 600 kW and 600 kVA are different ratings: at PF 0.8, 600 kW equals 750kVA. Use the correct row or formula.
AISIKAI SKT1 supports both 220V and 230V AC control supplies.
Check these five points before turning the calculated candidate into a final selection:
Check the load on mains power, too.
Some systems turn off less important equipment when the generator takes over. This allows a smaller generator to be used. But the transfer switch still needs to carry the full load when mains power is on
Temperature: High temperatures may reduce how much current the ATS can carry. Check the manufacturer’s guidance.
Future expansion: If you plan to add more equipment later, choose an ATS with extra capacity.
Protection: PC-class automatic transfer switches do not have built-in overload or short-circuit protection. Use suitable circuit breakers or fuses to provide this protection.
Poles and controls: confirm neutral switching, frequency, control voltage and the generator-start interface. The current calculation does not determine whether the system needs three or four poles.
Once you know the required amp rating, you can compare these options:
SKT1 motorized automatic transfer switch — up to 3200A.
ASKQ6 solenoid automatic transfer switch— up to 630A。
AISIKAI offers two options, both available up to 6300A:
ASKQ8: The ASKQ8 solenoid automatic transfer switch is available in ratings up to 6300A.
Two interlocked ACBs: This setup uses two air circuit breakers (ACBs), one for each power source. An interlock prevents both breakers from closing at the same time. A controller manages the automatic transfer.
We also offer complete automatic transfer switch cabinets. Tell us your required amp rating and site needs. We can build the cabinet with a suitable switch, controller and protection devices.
Yes. A higher-rated ATS is fine, but it does not let your generator power more equipment. Keep the total load within the generator’s rated capacity.
The current calculation is the same for both. AISIKAI SKT1 works with 50Hz and 60Hz. If you also need a controller, tell us the frequency when ordering so we can set it before delivery.
Send your generator nameplate or configurations to sales@aisikai.com.
Include a single-line diagram if available. Tell us whether you need a standalone switch or a complete ATS cabinet.